Specification of 380V/400V/415V Capacity 10-200kVA
Main Input
Input voltage 380V/400V/415V(line to line)
220V/230V /240V(line to neutral)
Input frequency 50/60Hz
Power factor >0.99
Input voltage window -20%~+25%
Frequency window 40-70Hz
Battery
Battery voltage ± 240VDC
Charger power 20%*Power
Charger voltage precision 1%
Bypass
Bypass voltage 380V/400V/415V, three phase
220V/230V/240V, one phase
Bypass voltage window -20%-+15%, full load, settable
Bypass overload capabiltiy 125%, long time operation
125%< load <130%, last for more than 1 hour
130%
Output
Output voltage 380V/400V/415V, three phase
220V/230V/240V, one phase
Voltage precision ± 0.5% (balance load), ± 1% (unbalance load)
Voltage THD(Total Harmonic Distortion) THD<1%(linear load), THD<5%(nonlinear load)
Power factor 0.8
Phase tolerance 120° ± 0.5° (balance and unalance load)
Crest factor 3: 1
Overload capabiltiy 105%, long time operation
110%, transfer to bypass after 1hour
125%, transfer to bypass after 10 minutes
150%, transfer to bypass after 1 minute
>150%, transfer to bypass after 200ms
System
System efficiency Normal mode: 95%
ECO mode: 99%
Battery mode efficiency 95%
Display LCD+LED, Touch screen and keyboard
IP class IP20
Interface (Communication Ports ) RS232, RS485, Dry contacts, SNMP card, EPO, Generator interface
Installation/Connection Top or bottom cable connection
Operation temperature 0-40centigrade
Storage temperature -25centigrade~70centigrade
Relative humidity 0-95% (non-comdensing)
Noise(dB) <55dB
Weight(KG) 6 -module cabinet RM060/10, RM090/15, RM120/20 150KG
10-module cabinet RM100/10, RM150/15, RM200/20 180KG
PM10 10kVA: 20KG
PM15 15kVA: 21KG
PM20 20kVA: 22KG
Dimension(W*D*H)(mm) 6-module cabinet 600*900*1600
10-module cabinet 600*900*2000
Module 400*600*133 (10kVA/15kVA/20kVA)
Specification of 200V/208V
Capacity 6-100kVA
Main Input
Input voltage 200V/208V (line to line)
Input frequency 50/60Hz
Power factor >0.99
Input voltage window -40%~+25%
Frequency window 40-70Hz
Battery
Battery voltage ± 240VDC
Charger power 20%*Power
Charger voltage precision 1%
Bypass
Bypass voltage 200V/208V, line to line
Bypass voltage window -20%-+15%, full load
Bypass overload capabiltiy 125%, long time operation
125%< load <130%, last for more than 1 hour
130%
Output
Output voltage 200V/208V, line to line
Voltage precision ± 1% (balance load), ± 2% (unbalance load)
Voltage THD(Total Harmonic Distortion) THD<2%(linear load), THD<5%(nonlinear load)
Power factor 0.9
Phase tolerance 120° ± 0.5° (balance and unalance load)
Crest factor 3: 1
Overload capabiltiy 105%, long time operation
110%, transfer to bypass after 1hour
125%, transfer to bypass after 10 minutes
150%, transfer to bypass after 1 minute
>150%, transfer to bypass after 200ms
System
System efficiency Normal mode: 90%
ECO mode: 99%
Battery mode efficiency 90%
Display LCD+LED, Touch screen and keyboard
IP class IP20
Interface (Communication Ports ) RS232, RS485, Dry contacts, SNMP card, EPO, Generator interface
Installation/Connection Top or bottom cable connection
Operation temperature 0-40centigrade
Storage temperature -25centigrade~70centigrade
Relative humidity 0-95% (non-comdensing)
Noise(dB) <55dB
Weight(KG) 6-module cabinet RM036/06L, RM060/10L 150KG
10-module cabinet RM100/10L 180KG
PM06L 6kVA: 20KG
PM10L 10kVA: 22KG
Dimension(W*D*H)(mm) 6-module cabinet 600*900*1600
10-module cabinet 600*900*2000
Module 430*600*134 (6kVA/10kVA)
Modular Online UPS (10-200kVA) (RM Series)